In the operation of industrial cold storage, Temperature and pressure gauges and dataloggers (self-recording thermometers) It is a mandatory "eyes and ears" measuring device for controlling the storage conditions of food, seafood, and medical pharmaceuticals according to standards. HACCP, ISO 22000 and GSP (Good Storage Practices). A small deviation in temperature monitoring can lead to the entire shipment being damaged or failing export inspection. Tan Long We provide and integrate a complete range of mechanical measuring instruments, digital controllers, and 24/7 remote IoT monitoring solutions that meet quality and measurement standards.
🏢 Tan Long's Automated Surveillance Solutions
Tan Long is an integrator of automated control and measurement systems for large-scale projects:
- ASRS NECS cold storage SCADA system (102,642 pallets): Manages over 500 real-time temperature, pressure, and humidity readings with an accuracy of ±0.1°C.
- Pharmaceutical warehouse meeting GSP standards: Temperature mapping monitoring, automatic SMS alerts, and an audible alarm when temperature fluctuations occur.
- Siemens/Schneider PLC control cabinets: Includes a digital clock and Modbus RS485 communication port.
1. Classification of Cold Storage Temperature Gauges and Devices
| Type of Measuring Device | Principles & Measurement Ranges | Outstanding Brand | Practical Applications |
|---|---|---|---|
| Mechanical thermometer (Metal pin / Capillary wire) | Bourdon tube or bimetallic strip, measuring range -50°C to +50°C, no power supply required. | Wika (Germany), Wise (Korea), Yamaki | Mount it outside the warehouse door or on the compressor housing for on-site visual observation. |
| Electronic digital controller & display | NTC/PT100 sensor, sharp LED display, compressor and defrost relay switching. | Dixell (Emerson – Italy), Carel (Italy), Elitech, Conotec | Installed on the main control panel of all industrial cold storage facilities. |
| Datalogger thermometer (GSP/HACCP standard) | Stores 16,000–32,000 measurement points, connects via USB port to export PDF/Excel reports. | Testo (Germany), Elitech RC-5+, LogTag (New Zealand) | Mandatory for warehouses storing medicines, vaccines, refrigerated vehicles, and seafood for export. |
| Remote wireless IoT monitoring system | Zigbee/LoRaWAN wireless sensors connect to the cloud, providing 24/7 alerts via SMS/App. | Tan Long SCADA, Siemens, Advantech | Large logistics center, multi-branch food distribution warehouse chain. |

2. Standards for Calibration and Verification of Cold Storage Meters According to State Regulations
- Periodic inspection requirements (Circular of the Ministry of Science and Technology): Temperature measuring devices used in food and pharmaceutical storage are required to have calibration certificates from reputable metrology centers (Quatest 1, Quatest 3, or the Metrology Institute's Testing Center).
- Accuracy allowed:
- Cold storage for food and seafood: Standard deviation should not exceed ±1.0°C.
- Pharmaceutical and vaccine cold storage (GSP): Strict standard deviation not exceeding ±0.5°C.
- Temperature Mapping Evaluation: Position the sensors at the most unfavorable points (near doorways, sheltered corners, highest points on shelves) to ensure there are no overheated areas.
3. Refrigerant Pressure Gauges (High & Low Pressure) for Operating Technicians
In addition to the warehouse air temperature gauge, industrial air conditioning systems are required to install pairs of... Oil pressure gauge, measuring suction pressure (low pressure) and discharge pressure (high pressure).:
- It helps engineers accurately monitor the condensation pressure and evaporation pressure of refrigerants (R22, R404A, R507A, NH3).
- Timely detection of gas shortages, clogged expansion valves, condenser buildup, or compressor overload is crucial for addressing issues before compressor fires or explosions occur.

4. Where to Install Temperature Sensors in a Cold Room
However accurate the instrument, a badly placed sensor will not reflect the true temperature of the goods. Some rules for installing sensors:
- Do not place it right at the evaporator air outlet: This spot is always colder than the real room temperature, so the controller cuts the compressor out early.
- Place it at a representative height and position: Usually about mid-height of the stacked goods, away from the door. Large rooms need several measuring points.
- Separate control sensors from monitoring sensors: The control sensor switches the equipment on and off. The monitoring sensor (datalogger) reflects product temperature for the records.
- Defrost sensor: Mounted on the evaporator to end the defrost cycle at the right time, avoiding over-long defrosts that warm the room.
5. Setting Up Dataloggers and Temperature Alarms
- Logging interval: Food stores usually log every 5–15 minutes. Pharmaceutical and vaccine stores may need a shorter interval under the company's GSP procedure.
- Alarm thresholds: Set high and low thresholds with a time delay so short door openings for loading do not raise false alarms.
- Alarm channels: Local siren and light combined with text messages or a phone app for the person in charge outside office hours.
- Record keeping: Temperature data must be kept for the period set by the quality management system, ready to present at HACCP or GSP audits or when a customer asks.
6. Daily Maintenance and Checks of Measuring Instruments
- Compare the instrument reading with a reference thermometer periodically and record the deviation.
- Check the datalogger battery, memory capacity and data connection.
- Check that sensor cables are not broken, crushed or soaked where they pass through the panel wall.
- Replace sensors that show large or erratic deviations; do not simply offset the reading.
Frequently Asked Questions
How often should a cold room thermometer be calibrated?
Normally once a year, or as set by the quality management system and customer requirements. GSP pharmaceutical stores usually have stricter requirements.
How do a datalogger and a temperature controller differ?
The controller uses sensors to switch the compressor, fans and defrost. The datalogger only records temperature over time as quality evidence. The two should be separate so the monitoring data is independent.
Can cold room temperature be monitored by phone?
Yes. IoT or SCADA monitoring systems let you view temperature, receive alarms and download reports remotely by phone or computer.