What is HVAC? Principles, structure and research documents of HVAC

HVAC is an engineered system integrating three functions — Heating, Ventilation and Air Conditioning — operating together to control temperature, humidity and air quality in an enclosed space. Its technical foundation rests on three sciences: thermodynamics, heat transfer and fluid mechanics.

In an industrial setting, an HVAC system does more than provide human comfort. For food plants, cold stores and pharmaceutical facilities, HVAC is a prerequisite for meeting HACCP food safety standards, GMP good manufacturing practice and ISO 14644 cleanroom classification. This article provides a comprehensive analysis of the construction, operating principle, system types and HVAC design standards applied in

What HVAC is and what each component means

What is HVAC? is always the first question investors ask when they start looking into environmental control solutions for factories and industrial buildings. The term stands for Heating, Ventilation and Air Conditioning. These three subsystems work closely together to maintain

  • Heating: This function supplies heat to a space when the outdoor temperature falls below the design threshold. In the Vietnamese market, the heating subsystem mainly serves specialist environments such as pharmaceutical cleanrooms, laboratories and northern factory areas in winter. The heat source is usually
  • Ventilation This subsystem replaces indoor air with fresh outdoor air to control CO2 concentration and remove odours and chemical vapours generated by the production line. Under ASHRAE 62.1, the minimum fresh air rate is strictly specified according to floor area and occupancy, typically ranging from 0
  • Air Conditioning: This is the process of adjusting the temperature and humidity of the incoming air stream to the design condition before distributing it into the room through equipment such as Condenser or AHUs. According to ASHRAE Energy Benchmarking, air conditioning is the most energy-intensive subsystem, accounting for 40% to 60% of the whole system's electricity consumption in industrial plants.
  • HVAC&R (Heating, Ventilation, Air Conditioning and Refrigeration): This term extends the scope to Refrigeration, covering systems such as Cold storage, freezing chambers and IQF conveyor. This is the core field in which Tan Long has established its position through key projects such as the NH3 refrigeration systems for Kyokuyo Vina Foods and the 12,000 MT cold storage project for Frescol Tuna Vietnam. In these systems, combining HVAC with equipment such as refrigeration compressor at large capacity is the key factor in sustaining operating performance.
  • HVACR (Heating, Ventilation, Air Conditioning, Refrigeration): This variant appears frequently in North American technical literature. It focuses directly on dedicated refrigeration equipment rather than general air quality control, helping engineers distinguish clearly between residential air conditioning and complex industrial refrigeration systems.
What is HVAC system? Principles, structure and research documents of HVAC
What is HVAC system? Principles, structure and research documents of HVAC

The history of HVAC systems

The modern air conditioning system originated with Willis Carrier's 1902 invention, when he designed equipment to control temperature and humidity for the Sackett-Wilhelms printing plant in New York, in order to keep printing paper stable through humid summers. The design built on the vapour condensation cooling principle that Michael Faraday had established

Nikolay Lvov, a Russian engineer, contributed the theory of natural ventilation in the 18th century, laying the foundation for later industrial ventilation systems. Coyne College in Chicago began training HVAC engineers in 1899, the first formal training programme in the field.

The industrial revolution drove demand for environmental control in textile mills, food plants and medical facilities. From the 1970s, ASHRAE standards began to systematise design requirements. From 2000 onwards, Building Automation Systems (BAS) integrated HVAC with PLC and SCADA, allowing automatic monitoring and adjustment

HVAC system construction and the function of each component

To understand clearly What is HVAC?, we need to analyse the construction from its three core subsystems. These subsystems comprise numerous items of equipment operating in a strict sequence to maintain the facility's air standards.

The structure of the HVAC system consists of 3 main parts
The structure of the HVAC system consists of 3 main parts

Air handling subsystem (Air Handling Unit)

The Air Handling Unit (AHU) is the heart of an HVAC system, performing four tasks in sequence: filtering, cooling or heating, humidifying or dehumidifying, and distribution. A standard AHU in a food plant comprises the following functional sections, fitted in this order:

IngredientFunctionReference specification
Fresh air damperControls how much outdoor air is admitted10 to 20% of total flow
Mixing boxMixes return air with outdoor airAdjusted by CO₂ sensor
Pre-filter (G4)Retains coarse dust, protects the coilFiltration efficiency ≥ 35% per EN 779
Fine filter (bag filter F7/F9)Retains fine PM₂.₅ dustEfficiency ≥ 80 to 95%
Cooling coilReduces air temperature and humidityTypical outlet temperature 12 to 14°C
Heating coilRaises the air to the room supply temperatureUsually 18 to 22°C
Supply fanCreates pressure and moves air through the ductworkStatic pressure 200 to 800 Pa
Filters trap dust and allergens in the air
Filters trap dust and allergens in the air

Refrigeration subsystem

The refrigeration subsystem supplies the cooling energy to the coils in the AHU. Depending on project scale, Tan Long recommends two main technology options:

  • Water chiller system: Usually applied to facilities below 500 kW. The system uses water chiller to circulate chilled water at 6°C to 12°C. The vapour-compression cycle takes place across four items of equipment: the compressor, the condenser, the expansion valve and the evaporator.
  • Industrial NH₃ refrigeration system: For food plants and large-scale cold storage (above 500 kW), an NH₃ system is the optimal choice. This technology delivers a COP of 3.5 to 5.5, saving 20% to 40% of electricity. Tan Long has successfully deployed this solution on major projects such as C.P. Vietnam and Lotte F&G Vietnam.

Air distribution subsystem

After treatment in the AHU, the air stream is carried through the ductwork to each area. A complete HVAC system must coordinate three air streams well:

  • Supply air: Carries clean, temperature- and humidity-conditioned air to the diffusers in the production room.
  • Return air: Recovers 80% to 90% of the air for re-treatment, reducing the load on the system and optimising operating cost.
  • Exhaust air: Removes polluted air, chemical vapours or micro-organisms to the outside environment.

Tan Long's design practice favours the equal friction method, keeping air velocity in the main duct at 5 to 8 m/s to limit noise and vibration.

BAS/PLC control system

In the industry 4.0 era, understanding What is HVAC? must include automatic control. Tan Long integrates a BAS building management system together with PLC control and SCADA control panels.

This solution allows real-time monitoring of temperature, humidity and differential pressure. In particular, applying VFDs to the supply fans lets the system adjust capacity automatically to actual demand, cutting electricity consumption by 20% to 40% compared with traditional fixed-speed systems.

How an HVAC system works

To understand how What is HVAC?operates optimally, we need to look at the closed loop that treats air continuously through four sequential technical steps. This process keeps the production and storage environment within standard for temperature, humidity and cleanliness.

  • Step 1: Air intake and mixing: The system begins by drawing outdoor air through the fresh air damper, then mixing it with part of the return air from the room. The mixing ratio is calculated strictly against ASHRAE 62.1 and the actual CO2 concentration. When the sensor measures a CO2 concentration above the 1,000 ppm threshold, the control system automatically increases the fresh air proportion to keep staff safe and protect product quality.
  • Step 2: Temperature and humidity treatment at the central unit: The mixed air stream passes through the AHU for a sequence of physical processes: pre-filtration, deep cooling to the dew point to remove moisture, then reheating to the design supply temperature. Temperature is usually held at 16°C to 18°C for cooling or 30°C to 35°C for heating. At food plants, condenser at large capacity combined with refrigeration compressor unit is the key to controlling these parameters accurately on the psychrometric chart.
  • Step 3: Air distribution through the ductwork: Once treated to standard, the air is carried through the ductwork and diffusers to each functional zone. On modern projects, Tan Long usually applies a VAV (Variable Air Volume) system to vary airflow flexibly according to each area's actual demand, optimising electricity consumption across the whole facility.
  • Step 4: Return air recovery and energy regeneration: At the end of the cycle, room air is returned to the AHU to begin a new loop. For cold storage systems or large-scale workshops, we also fit a heat recovery unit to use the energy in the exhaust air stream to pre-treat the incoming fresh air. This reduces the thermal load on the cooling coils by 20% to 30%, delivering strong economic returns for the investor.

HVAC system types and a comparison of the common configurations

There are four main HVAC system types, each suited to a different facility scale and requirement.

System typeHeat transfer mediumSuitable scaleEnergy efficiencyTypical applications
Central HVAC (Chiller + AHU)Chilled water 6 to 12°CMedium to large, above 200 kWHigh (COP 4 to 6)Factories, hospitals, shopping centres
Split/Multi-splitDirect RefrigerantSmall, below 50 kWMedium (EER 2.5 to 3.5)Offices, households
VRV/VRFVariable flow refrigerantMedium, 50 to 300 kWHigh (SEER up to 6.5)Hotels, office buildings
Packaged unitDirect RefrigerantSmall to mediumMediumSmall workshops, schools

VRV/VRF (Variable Refrigerant Volume/Flow) systems use an inverter compressor to vary the refrigerant flow to each FCU (Fan Coil Unit) according to actual demand. The difference from a central chiller system is that VRV/VRF needs no chilled water pumps or cooling tower, saving

For food plants and industrial cold storage, a central HVAC system using a chiller combined with NH₃ is the best choice on long-term operating cost, thanks to its higher COP and equipment life of more than 20 years.

HVAC applications in industry and commercial buildings

Industrial HVAC systems serve more demanding requirements than residential HVAC, particularly on contamination control, maintaining differential pressure and complying with industry standards.

 HVAC plays a role in providing the best air quality
HVAC plays a role in providing the best air quality

HVAC in food plants and cold stores

HACCP and FSSC 22000 require temperature, humidity and air quality to be controlled by cross-contamination risk zone. High-care food processing zones must hold a room temperature of 10 to 12°C, relative humidity below 65%, and positive pressure relative to surrounding areas to stop contaminated air entering

Tan Long has designed refrigeration and HVAC systems for Vietnam Clean Seafood JSC at An Nghiep Industrial Park (Soc Trang) and C.P. Vietnam Livestock JSC at Tan Phu Trung Industrial Park, fully meeting the technical requirements for temperature control and contamination prevention.

HVAC in GMP pharmaceutical cleanrooms

GMP (Good Manufacturing Practice) cleanrooms impose the most demanding HVAC requirements of any industrial application. The three core parameters to control closely are:

Air changes per hour (ACH) range from 20 to 250 per hour depending on cleanroom grade. An EU GMP Grade D room requires a minimum of 20 ACH. A Grade A room (equivalent to ISO 5) requires unidirectional airflow at 0.36 to 0.54 m/s per ASHRAE 209.

Temperature and humidity are held in a narrow band of 20 to 22°C and 40 to 60% RH to protect the stability of pharmaceuticals and production materials.

A differential pressure cascade, with pressure decreasing from clean areas towards dirty areas, each step differing by 12.5 Pa per WHO guidance. Grade A/B cleanrooms maintain positive pressure of 15 Pa relative to the corridor. Areas producing hazardous (cytotoxic) materials maintain negative pressure to stop hazardous substances escaping.

HVAC in electronics and semiconductor cleanrooms

Electronics cleanrooms are classified under ISO 14644-1, from ISO 9 (ordinary cleanroom) to ISO 1 (ultra-clean room for chip manufacturing). Classification is based on the number of dust particles per cubic metre of air at particle sizes from 0.1 to 5 microns

HVAC design standards in Vietnam and internationally

HVAC design in Vietnam must follow a three-layer standards system: national, regional and international.

StandardScope of applicationMain content
TCVN 5687:2010Mandatory in VietnamVentilation, air conditioning and heating for buildings
ASHRAE 62.1International referenceMinimum outdoor air rates for indoor air quality
ASHRAE 90.1International referenceEnergy efficiency for commercial and industrial buildings
ISO 14644-1Clean roomCleanroom classification by particle density
GMP WHO Annex 2Pharmaceutical manufacturingHVAC requirements for medicine manufacturing facilities
GMP EU Annex 1Sterile pharmaceutical manufacturingHVAC design for cleanrooms producing injectables and eye drops

TCVN 5687:2010 is mandatory for every building in Vietnam. The standard specifies design outdoor temperatures by climate zone, required indoor temperature and humidity, methods for calculating cooling and heating loads, and filtration and air quality requirements.

The number of air changes is usually determined in a period of time.
The number of air changes is usually determined in a period of time.

HVAC energy efficiency: COP, EER, SEER and IPLV

The energy efficiency of HVAC equipment is assessed through four technical indices, each applying to different operating conditions.

  • COP (Coefficient of Performance) is the ratio between the cooling or heating energy produced (kW) and the electricity consumed (kW). Modern central chillers achieve a COP of 5.5 to 7.0 at nominal conditions (chilled water 12°C in, 7°C out; condenser water 30°C in, 35°C out). By comparison, NH₃ systems achieve a COP of 3.5 to 5.5 at temperatures
  • EER (Energy Efficiency Ratio) measures efficiency at nominal conditions (35°C outdoor temperature), in BTU/h/W or W/W. Air conditioners achieving an EER above 3.5 (equivalent to 12 BTU/h/W) are considered high efficiency under Energy Star standards.
  • SEER (Seasonal Energy Efficiency Ratio) measures average efficiency across a season, reflecting actual operating cost more closely because it accounts for variation in cooling load and outdoor temperature throughout the cooling season. The minimum SEER requirement in the USA from 2023 is 14 for split systems in the south, equivalent to
  • IPLV (Integrated Part-Load Value) assesses chiller performance at four part-load points (25%, 50%, 75% and 100%), reflecting real operating efficiency accurately because buildings run at full load for only 1 to 5% of total operating hours.
Trade show of the refrigeration industry
Trade show of the refrigeration industry

HVAC system maintenance: schedule and standard procedure

Scheduled HVAC maintenance sustains design performance and extends equipment life to 15 to 25 years, against 8 to 12 years without proper servicing. The maintenance plan is divided into three frequencies.

  • Monthly maintenance covers checking and replacing G4 pre-filters, cleaning FCU filter screens, checking fan belt condition, measuring temperature and humidity at fixed measuring points, and checking for abnormal noise and vibration.
  • Quarterly maintenance covers replacing F7/F9 secondary filters in the AHU, cleaning the cooling coil with specialist chemicals (no strong acids, to avoid corroding the aluminium), checking and tightening electrical connections in the control panel, measuring chilled water pump inlet and outlet pressures, and checking water concentration and pH in the expansion vessel.
  • Annual maintenance covers checking and topping up refrigerant (if pressure is 10% below the design value), calibrating temperature and humidity sensors, checking all valves, dampers and actuators, measuring airflow at the diffusers and comparing it with design values, and testing HEPA filters by DOP (Dispersed Oil Particulate) test per ISO 14644-3.

HVAC system design software

Designing a complete industrial HVAC system requires several specialist software packages across the different stages.

  • Cooling load calculation uses Trace 700 (Trane) or HAP (Carrier) following ASHRAE's RTSM (Radiant Time Series Method). Trace 700 supports hourly building energy simulation across the year and produces detailed ASHRAE 90.1 reports. Heatload is popular domestically, with a Vietnamese interface suited to small and medium projects.
  • Duct sizing uses Duct Checker and the ASHRAE Duct Fitting Database to calculate local pressure losses at bends, tees and control dampers. Revit MEP (Autodesk) is the standard BIM platform for multidisciplinary coordination (HVAC, electrical, plumbing) on large projects, enabling clash detection between building services.
  • AHU and equipment selection uses manufacturers' selection software such as Carrier ESP Plus, Daikin VRV Designer and McQuay Select. These packages calculate fan characteristic curves and the optimal operating point, and generate installation drawings automatically.

Designing and installing industrial HVAC systems with Tan Long

Tan Long is a consultant, designer and installer of industrial refrigeration systems with more than 20 years of experience in Vietnam. Our engineering team has completed more than 200 projects, from 12,000 MT cold stores and IQF freezing lines for seafood plants to NH₃ refrigeration systems for major food groups in Vietnam such as C.P., Lotte F&G, Kyokuyo Vina Foods and Frescol Tuna.

Every Tan Long HVAC and refrigeration project goes through a design process that ensures compliance with TCVN 5687:2010, ASHRAE and the relevant industry standards. We provide complete DQ/IQ/OQ technical documentation for projects requiring GMP and HACCP.

Contact Tan Long on (+84) 908 895 679 (Mr. Chinh) or (+84) 982 330 357 (Mr. Sang) for advice on designing an HVAC system suited to the scale and standards of your project.

Frequently asked questions about HVAC systems

How does HVAC differ from ordinary air conditioning?

An ordinary air conditioner (split unit) only cools or heats a single zone. An HVAC system integrates all three functions — heating, ventilation and air conditioning — while also filtering, controlling humidity, maintaining differential pressure and distributing fresh air to technical standards. HVAC is a whole-facility engineering solution, not a single piece of equipment.

How much does an industrial HVAC system cost to install?

The cost depends on capacity, cleanroom grade and the equipment selected. From Tan Long's delivery experience, an HVAC system for a 1,000 m² food plant typically ranges from 1.5 to 4 billion VND, depending on the level of automation and the standards required. A GMP cleanroom HVAC system costs 2 to 3 times more because of HEPA filtration and differential pressure control. Contact Tan Long for advice and a detailed quotation based on your actual project.

How often does an HVAC system need maintenance?

G4 pre-filters are replaced monthly. F7/F9 secondary filters every 3 months. The cooling coil is cleaned every 3 to 6 months. A full system check and calibration of measuring instruments is carried out every 12 months. HEPA filter integrity is tested to ISO 14644-3 every 6 months.

What is the difference between HVAC and HVACR?

HVAC encompasses heating, ventilation, and air conditioning, applicable to both residential and commercial buildings. HVAC&R or HVACR extends to refrigeration systems, including cold storage and freezers., IQF conveyor and industrial freezing lines. Tan Long specializes in HVAC&R for food factories, cold storage facilities, and seafood processing plants.

Which standards apply to pharmaceutical plant HVAC in Vietnam?

Pharmaceutical plants in Vietnam must comply simultaneously with TCVN 5687:2010 (building standard), WHO GMP Annex 2 (pharmaceutical cleanroom HVAC requirements) and EU GMP Annex 1 if exporting to Europe. The Drug Administration of Vietnam (DAV) requires detailed HVAC design documentation (DQ/IQ/OQ/PQ) as part of the manufacturing licence application.

Frequently asked questions about HVAC systems

What is HVAC?

HVAC stands for Heating, Ventilation and Air Conditioning — a system integrating those three functions to control temperature, humidity and air quality in a building.

What subsystems make up HVAC?

Three main subsystems: heating, ventilation and air conditioning, together with the air handling subsystem (AHU), the ductwork, the pipework and the monitoring and control system.

How does HVAC differ from an industrial refrigeration system?

HVAC aims at comfort and air quality for people in a building. An industrial refrigeration system aims at preserving and processing products, usually at far lower temperatures and running continuously to meet production demand.

What kinds of facility need an HVAC system?

Office buildings, shopping centres, hotels, hospitals, pharmaceutical and electronics plants — anywhere that needs temperature, humidity and air cleanliness controlled together.

On what criteria should an HVAC system be chosen?

On the facility's heat load, the number of zones needing independent control, the cleanliness and humidity requirements, the space available for equipment, and the investment and long-term operating costs.